Q & A of the Day – Can I use T&E cable for this sub-distribution board CPC?

BookmarkThis 07.02.2012
ECA
 

Jamie Harrison asks about the earthing of sub-distribution board earth CPC and the cables that could be used for it. His question is answered by the ECA (Theme – Cables and Wiring):

10mm twin & earth cable should be OK.
10mm twin & earth cable should be OK.
pixel
Question: If one feeds a sub-distribution board, say to an internal garage or workshop - and it is dependent on the load, are PVC 6mm or PVC 10mm twin & earth (T&E) cables suitable for the earth circuit protective conductor (CPC) as long as all the test parameters are satisfied?

Answer: Normally yes, so long as the equation in Regulation 543.1.3 is satisfied, and that the disconnection time is met.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
The Electrical Contractors' Association (ECA)
ECA Head Office, ESCA House,
34 Palace Court, London W2 4HY
Tel: 020 7313 4800
Fax: 020 7221 7344
Email: electricalcontractors@eca.co.uk
Web: www.eca.co.uk
blue arrow pointing right   ECA

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: ECA & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Is this 1970s electrical installation still OK today?
Q & A of the Day - Please clarify how to connect this smoke alarm circuit?
Q & A of the Day - Should a wind turbine supply cable be earthed both ends?
Q & A of the Day – What testing is needed for this altered domestic kitchen circuit?
Q & A of the Day – Is this garage sub-distribution board earth CPC adequate?
Q & A of the Day – Are smoke detectors necessary for this toilet?
Q & A of the Day – Can I use this T&E cable as the sub-distribution board CPC?
Q & A of the Day – What connection for this circuit having an extra consumer unit?