Q & A of the Day – Should I work to minimum luminaire voltage tolerances?

BookmarkThis 17.01.2012
NICEIC
 

This question is about the 17th Edition and whether it is permissible work to minimum luminaire voltage tolerances rather than percentage drops. It is answered by the NICEIC (Theme - Lighting):

Referr to Regs 525.1 and 525.3.
Referr to Regs 525.1 and 525.3.
pixel
This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.

Question: In BS7671:2008 it gives a maximum voltage drop on a lighting circuit on a public supplied system as 3% (Table 12A - i). Would it be permissible to ignore this value and work to the minimum luminaire voltage tolerances?

For example, with a luminaire having a HF ballast able to work down to a minimum voltage of 200V, and working to the lowest allowed supply voltage of 216.2V ( Uo - 6%), can it be allowed to have an absolute maximum voltage drop of 16.1V (Uo - 7%).

I would never design using maximum limits but, if I was to design ensuring that I am within the safe working limits of the luminaire, I could use a larger voltage drop than the 3% stated in BS7671. As far as I can see from looking through BS7671, I cannot find any note saying that I can work to the voltage tolerances of equipment supplied, instead of Table 12A.

Answer: Referring to Regulation 525.1 (p106) of BS7671:2008 requires the voltage at the terminals of equipment to be greater than the lower limit specified in the product standard for the equipment concerned. So, if these conditions were ensured, then this would comply with BS7671:2008.

The percentage approach, given in Regulation 525.3, is usually applied where specific information concerning the load is unavailable at the time of design and hence is more onerous.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
NICEIC Group Ltd.,
Warwick House, Houghton Hall Park,
Houghton Regis, Dunstable LU5 5ZX
Tel: +44 (0)1582 531 000
Fax: +44 (0)1582 531 010
Email: enquiries@niceic.com
Web: www.niceic.com
blue arrow pointing right   NICEIC

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: NICEIC & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – What are requirements for stationary equipment periodic inspection?
Q & A of the Day – Why bond to a plastic gas pipe?
Q & A of the Day – Must I install one double-pole isolator for two consumer units?
Q & A of the Day – What should be the extent of electrical testing in a wooden chalet?
Q & A of the Day – Which code for a batten holder found in a domestic bathroom zone?
Q & A of the Day – Should I use equipotential bonding in a wooden clubhouse?
Q & A of the Day – Are we now allowed to calculate R1+R2 only?
Q & A of the Day – Why is there a delay in EICR forms from scheme providers?
Q & A of the Day – Is there an individual certificate for disabled toilet alarms?