Q & A of the Day – Can PVC cables in polystyrene insulation run in PVC conduit?

BookmarkThis 29.12.2011
SELECT
 

David Castle asks whether PVC cables in contact with polystyrene insulation can be safely run in PVC conduit. His question is answered by SELECT:

PVC cables in contact with polystyrene?
PVC cables in contact with polystyrene?
pixel
This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.

Question: In the installation I’m working on, PVC cables running through, and in contact with, polystyrene insulation need to be run in conduit - can this be PVC conduit?

Answer: Expanded polystyrene is known to have an effect on thermoplastic insulated cables, caused by the softening of the cables insulation by chemicals in the polystyrene insulation. The same sort of degradation is possible with other thermoplastic materials.

Therefore, checks will have to be made with manufacturer of the PVC conduit.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?