Q & A of the Day – Can armoured cable be placed in conduit?

BookmarkThis 14.12.2011
BASEC (The British Approvals Service for Cables)
 

John Russell asks about whether an armoured cable be laid in a PVC conduit. His question is answered by BASEC (Theme - Cables, Wiring & Wiring Accessories):

Can armoured cable be laid in PVC conduit .
Can armoured cable be laid in PVC conduit .
pixel
This Q & A is one of thousands posted in our Technical Expertise area, and answered on a daily basis by our Voltimum Experts.

Question: Can an armoured cable be laid in a PVC conduit for aesthetic purposes?

Answer: PVC sheathed armoured cable could be placed in PVC conduit. A PVC sheathed armoured cable - such as BS 5467 - could be enclosed in a PVC conduit with few ill-effects.

However, if the cable is a low smoke halogen free type (e.g., BS 6724), or has specific fire performance (e.g., BS 7846), then the use of a PVC conduit could have deleterious effects on the cable in a fire, and guidance should be sought from the cable manufacturer concerned.

Other types of conduit may be more suitable.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
Contact: Dr Jeremy Hodge
The British Approvals Service for Cables (BASEC)
23 Presley Way, Crownhill,
Milton Keynes MK8 0ES
Tel: 01908 267300
Fax: 01908 267255
Email: mail@basec.org.uk
Web: www.basec.org.uk
blue arrow pointing right   BASEC

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: BASEC & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can armoured cable be placed in PVC conduit?
Q & A of the Day – Should there be a separate CPC in parallel with cable armour?
Q & A of the Day - Can PVC cable protection be damaged by other insulation types?
Q & A of the Day - For extension lead three-core flex, is there a colour requirement ?
Q & A of the Day - What is the best cable to use for sub-mains?
Q & A of the Day - Is 2.5mm2 stranded twin & earth cable OK in this house?
Q & A of the Day - Why is this conductor insulation lighting my neon screwdriver?
Q & A of the Day - Extensions using SY braided cables - can the 16A plugs be right?