Q & A of the Day - With this genset, would the circuitry provide a suitable earth?

BookmarkThis 05.10.2011
SELECT
 

Scott Dunbar asks about earthing a generator supply to an existing mains circuit and the safety of its earthing arrangements. His question is answered by SELECT (Theme - Fire and Safety):

Does the circuitry provide a suitable earth?
Does the circuitry provide a suitable earth?
pixel
This Question & Answer of the Day is one of thousands answered on a daily basis by our Voltimum Experts.

Question: I have been asked to wire an emergency generator supply to an existing mains circuit that supplies two freezers and a fridge freezer. The house supply is TN-C-S

I intend installing a two-pole two-way switch with a mid position 'OFF' to switch phase and neutral. The generator will be earthed with an earthing rod and with the neutral and earth linked within the 16A plug.

In the event that a mains failure occurs and the grid earth is broken would you agree that this circuitry provides a suitable earth?

I have obtained several opinions on the earthing of generators but there doesn't seem to be a consistent response!

Answer: With the standby emergency generator system that you describe, the generator does require a separate earth electrode, so that each source operates independently of the other. The earth electrode resistance should not exceed 20 ohms.

There is no requirement to link the neutral and earth at the plug, as operation in parallel with the incoming supply should not be possible. Therefore, the generator neutral should be connected to the generator framework, which will be earthed via the earth electrode and the main earthing terminal.

The generator supply would, in effect, be a TN-S supply. However, where the supply is PME, there may be no requirement to isolate both poles.

Further information could be obtained from BS 7671:2008 Chapter 55 and Regulation 551.6. See also BS 7430 'Code of Practice for Earthing'.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?