Q & A of the Day - Should this cable pass through this consumer unit?

BookmarkThis 29.09.2011
SELECT
 

D.B. McIntyre asks whether there should be concern over a cable passing through the consumer unit in a flat, since if the consumer unit's main switch was turned off, the cable would not be isolated. His question is answered by SELECT (Theme - Regulations and Legislation):

Should the cable pass through the CU?
Should the cable pass through the CU?
pixel

This Q & A is one of thousands posted in our Technical Expertise area, and answered a daily basis by our Voltimum Experts.

Question: We are carrying out a Periodic Inspection Report (PIR) on a domestic flat. The supply to the flat is from a central distribution board, while the sub-mains supplying the flat comes in through the back of the consumer unit, then goes out the bottom of it into a private landlord's meter. The cable then goes back to supply the consumer unit.

We are wondering if there should be concern over the cable passing through the consumer unit, as there may be confusion if somebody switches off the main switch on the consumer unit - and then presumes that the cable has been isolated, which it will not have been.

Answer: This is not an ideal situation and you are correct to highlight your concern.

Regulation 514.11.1 requires a warning notice to be fixed in each position where there are live parts present that are not capable of being isolated by a single device.

The location of the isolator should be indicated unless there is no possibility of confusion.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?