Q & A of the Day – Is there an advantage in breaking the neutral on a switch?

BookmarkThis 04.08.2011
Eaton
 

This Question of the Day, concerning isolation of the neutral, is answered by Eaton: (theme - Distribution Equipment):

Neutral currents can be considerable...
Neutral currents can be considerable...
pixel
This question, and thousands of others, have been answered by our Voltimum Experts on a daily basis in the Technical Expertise area.

Question: What is the advantage, or purpose, of breaking the neutral on a switch?

Answer: Isolation of the neutral prevents possible contact with live conductors on the load side of a switch. If the neutral is connected to earth by a cable or busbar of low impedance, then the neutral should be virtually at earth potential and safe.

However, with highly inductive loads such as supplying the primary side of power supply transformers and out of balance three-phase loads, neutral currents can be considerable - instead of virtually zero as with a well-balanced resistive load. This results in voltage appearing on the neutral and is typical of supplies today. Therefore, isolation of the neutral, as well as the phase, renders the load side of the switch totally safe to work on.

Also, the neutral should make first, break last in any switching operation, as the neutral provides the voltage reference point for the three-phases. Without this, phase-to-phase voltage may drift from 400V to considerably greater across one pair of phases, with damage liable to 400V equipment on the load side.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
Eaton
Reddings Lane, Tyseley,
Birmingham B11 3EZ
Tel: 08700 545 333
Fax: 0121 706 2012
Email: ukcommorders@eaton.com
Web: www.eatonelectrical.com
blue arrow pointing right   Eaton

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: Eaton & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – What are the difference types of automatic transfer switch (ATS)?
Q & A of the Day - Is breaking the neutral on a switch beneficial?
Q & A of the Day – Why not use an RCD in a TN-C earthing system?
Q & A of the Day - Can I reduce the cable lengths of an SPD?
Q & A of the Day – Must I separately link earth bars on this dis-board?
Q & A of the Day – Are LEDs dimmable?
Q & A of the Day - Can I reduce the cable lengths of an SPD?
Q & A of the Day - Why can't I use an RCD in a TN-C earthing system?