Q & A of the Day - Must we run an earth wire from house to external gas meter?

BookmarkThis 11.07.2011
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning a house with an outside gas meter some distance away, is answered by SELECT:

Earth from house to gas meter? (photo Kingsley)
Earth from house to gas meter? (photo Kingsley)
pixel
Question: We are currently wiring a new build house in North Berwick. The gas meter is going to be 150m from the house. Note that the gas pipe to and from the meter will be plastic.

Do we have to run an earth wire from the house to the gas meter?

Answer: With reference to Regulation 544.1.2, in such circumstance the main equipotential bond should - where practicable - be within 600mm of the point of entry of the service to the building if the meter is external.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?