Q & A of the Day - Should we use a second power service for air-conditioning?

BookmarkThis 23.06.2011
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning a building having two REC incoming LV electrical supplies, is answered by the ECA:

A second supply for the air-conditioning?
A second supply for the air-conditioning?
pixel
Question: We are currently fitting out a building where we already have lighting and power services recently installed, which is connected to the main low voltage system served by the REC LV supply. There is a second REC incoming LV electrical supply that enters the opposite end of the building that is still live.

Is it possible to use this second supply to serve the new air-conditioning system we are putting in?

Is it just the case of labelling both supplies and the sub-distribution boards in the areas being air-conditioned, together with linking the earthing systems. I'm not aware of anything in the regulations that may stop us considering this.

Answer: It is possible to have two supplies serving a building, subject to the installation being in accordance with BS 7671:2008 and the local DNO requirements.

Proper labelling is indeed what's needed. A notice at the origin stating the location of the other supply is also a good idea.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
The Electrical Contractors' Association (ECA)
ECA Head Office, ESCA House,
34 Palace Court, London W2 4HY
Tel: 020 7313 4800
Fax: 020 7221 7344
Email: electricalcontractors@eca.co.uk
Web: www.eca.co.uk
blue arrow pointing right   ECA

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Related information

Related contacts

More News...

Q & A of the Day – What are requirements for stationary equipment periodic inspection?
Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Is this 1970s electrical installation still OK today?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day - Please clarify how to connect this smoke alarm circuit?
Q & A of the Day - Should a wind turbine supply cable be earthed both ends?
Q & A of the Day – What are the difference types of automatic transfer switch (ATS)?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?