Q & A of the Day - Can we avoid having to buy seven RCBOs?

BookmarkThis 15.04.2011
ABB
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning a recommendation to fit a number of RCBOs and whether an RCD incomer might suffice, is answered by ABB:

Can we avoid buying seven RCBOs?
Can we avoid buying seven RCBOs?
pixel
Question: Following a periodical test carried out in our restaurant, we have been advised that the breakers protecting the socket circuits in the bar, kitchens and restaurant - fitted into the consumer unit - be changed to RCBOs.

We need seven in total, which comes to around £350 materials only. Is there another way around this? For example, could we fit an RCD switch to cover the whole unit?

Answer: From an installation perspective it is not in line with the guidance from the Wiring Regulations (BS7671:2008) to supply the whole distribution board (consumer unit) with an RCD incomer, as an earth fault in any circuit will cause the whole board to be lost. This may have health and safety implications if the board supplies lighting or fire/smoke alarms.

For further advice as to the optimum correct solution, you may wish to contact the ECA or NICEIC via the Voltimum website.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
ABB Ltd.,
Tower Court, Foleshill Enterprise Park,
Courtaulds Way, Coventry CV6 5NX
Tel: 02476 368500
Fax: 02476 364499
Email: lv.enquiries@gb.abb.com
Web: www.abb.co.uk
blue arrow pointing right   ABB

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: ABB & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Is there an energy benefit with softstarts over DOL starting?
Q & A of the Day – Is an oil container needed beneath an oil filled transformer?
Q & A of the Day – With a star delta motor, how do I reverse its direction of rotation?
Q & A of the Day – What is a BMS? What is EIB?
Q & A of the Day - Do switchgear / service points have distance requirements?
Q & A of the Day - For PFC capacitors, how do I calculate kVAr?
Q & A of the Day - Should I test RCBOs at the distribution board?
Q & A of the Day - Why does this freezer fuse keep blowing?
Q & A of the Day - Is this motor re-wind faulty?