Q & A of the Day - Are these shower electrical circuit readings OK?

BookmarkThis 14.04.2011
NICEIC
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning the Zs and Ze readings on a shower circuit, is answered by the NICEIC:

The local DNO should be advised!
The local DNO should be advised!
pixel
Question: What would be the correct remedy if the Zs reading on a shower circuit is 2.14, the Ze is 2.01, and the maximum permitted on a BS 60898 type B 40 MCB is 1.15?

Answer: If your Ze is at 2.01 ohms, then unless it is a TT system - which will require RCD protection - then the local DNO should be advised to resolve the situation.

If all circuits are protected by an RCD, then the maximum Zs value should be obtained from Table 41.5 (page 50) of the current Regulations regarding TT earthing arrangements.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
NICEIC Group Ltd.,
Warwick House, Houghton Hall Park,
Houghton Regis, Dunstable LU5 5ZX
Tel: +44 (0) 1582 531000
Fax: +44 (0) 1582 531010
Email: enquiries@niceic.com
Web: www.niceic.com
blue arrow pointing right   NICEIC

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: NICEIC & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – What are requirements for stationary equipment periodic inspection?
Q & A of the Day – Why bond to a plastic gas pipe?
Q & A of the Day – Must I install one double-pole isolator for two consumer units?
Q & A of the Day – What should be the extent of electrical testing in a wooden chalet?
Q & A of the Day – Which code for a batten holder found in a domestic bathroom zone?
Q & A of the Day – Should I use equipotential bonding in a wooden clubhouse?
Q & A of the Day – Are we now allowed to calculate R1+R2 only?
Q & A of the Day – Why is there a delay in EICR forms from scheme providers?
Q & A of the Day – Is there an individual certificate for disabled toilet alarms?