Q & A of the Day - How do I set a DOL starter motor overload relay?

BookmarkThis 11.04.2011
ABB
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning an induction motor overload relay and its setting, is answered by ABB:

An ABB motor starter overload relay.
An ABB motor starter overload relay.
pixel
Question: How do you set the motor overload relay for a Direct Online (DOL) starter for an induction motor? Is there a factor/term that one can multiply the full load current by, in order to set it (slightly above) the full load current?

Answer: The overload should be set to the motor rating plate full load current. There is no factor applied to the set point for DOL starting. Any factoring to allow for starting currents or overload situations during running is allowed for within the overload relay itself.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
ABB Ltd.,
Tower Court, Foleshill Enterprise Park,
Courtaulds Way, Coventry CV6 5NX
Tel: 02476 368500
Fax: 02476 364499
Email: lv.enquiries@gb.abb.com
Web: www.abb.co.uk
blue arrow pointing right   ABB

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: ABB & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Is there an energy benefit with softstarts over DOL starting?
Q & A of the Day – Is an oil container needed beneath an oil filled transformer?
Q & A of the Day – With a star delta motor, how do I reverse its direction of rotation?
Q & A of the Day – What is a BMS? What is EIB?
Q & A of the Day - Do switchgear / service points have distance requirements?
Q & A of the Day - For PFC capacitors, how do I calculate kVAr?
Q & A of the Day - Should I test RCBOs at the distribution board?
Q & A of the Day - Why does this freezer fuse keep blowing?
Q & A of the Day - Is this motor re-wind faulty?