Q & A of the Day - Can I use 13A sockets as local isolation?

BookmarkThis 29.03.2011
NICEIC
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning a general lighting system in a factory and the use of metalclad 13A sockets as local isolation, is answered by the NICEIC:

A  plug & socket can be a means of isolation.
A plug & socket can be a means of isolation.
pixel
Question: I'm designing a general lighting system in a factory where current lighting is afforded by highbay fittings. The manager in charge of the project is integrating energy efficient lighting luminaires with occupancy PIR detection, and these units will be plugged into metalclad 1 gang 13A switched socket outlets fixed to the lighting trunking. The circuits feeding these luminaires are to be protected by Merlin Gerin MCBs conforming with BS 60898.

The manager's 'manager' does not want a huge switchbank or contactors on the wall and just wants the circuits to be fed directly from the MCBs in the distribution board.

Is this permissible as regards local isolation being afforded by the 13A socket outlets? Or is it necessary to have to have switches at an accessible height to satisfy the regulations?

Answer: Under table 53.2 (page 117) of BS7671:2008, a plug and socket is deemed to be a means of isolation. We would, however, recommend that specific plug and sockets for the lighting application be installed to stop the use of these sockets for general use.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
NICEIC Group Ltd.,
Warwick House, Houghton Hall Park,
Houghton Regis, Dunstable LU5 5ZX
Tel: +44 (0)1582 531 000
Fax: +44 (0)1582 531 010
Email: enquiries@niceic.com
Web: www.niceic.com
blue arrow pointing right   NICEIC

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: NICEIC & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – What are requirements for stationary equipment periodic inspection?
Q & A of the Day – Why bond to a plastic gas pipe?
Q & A of the Day – Must I install one double-pole isolator for two consumer units?
Q & A of the Day – What should be the extent of electrical testing in a wooden chalet?
Q & A of the Day – Which code for a batten holder found in a domestic bathroom zone?
Q & A of the Day – Should I use equipotential bonding in a wooden clubhouse?
Q & A of the Day – Are we now allowed to calculate R1+R2 only?
Q & A of the Day – Why is there a delay in EICR forms from scheme providers?
Q & A of the Day – Is there an individual certificate for disabled toilet alarms?