Q & A of the Day - Extensions using SY braided cables - can the 16A plugs be right?

BookmarkThis 24.11.2010
BASEC (The British Approvals Service for Cables)
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning potentially hazardous use of SY braided extension cables with 16A plugs outdoors, is answered by BASEC:

Question: I saw some extension cables supplying power to outside equipment the other day. The cables were braided, but the braids were cut off and taped at the 16A plugs and sockets. Surely this cannot be right? In any case, how are you supposed to terminate the braids if you are going into a plastic plug/enclosure?

Answer: Don't use standard plugs - you are correct in identifying the hazard!

Standard indoor 13A plugs are not designed to be used with braided cables, but only with three core (brown, blue, green/yellow) flex. Standard industrial plugs and sockets are, likewise, not generally designed to accommodate a steel braid.

If it is felt that a steel braided flexible cable should be used because of the greater physical protection offered (such as SY type), then an appropriate plug / socket system must be used, with the appropriate gland and termination for the braid. These plugs are available from specialist suppliers. The braid needs to be bonded to earth.

If the braid is cut off and taped outside the plug, then there will be an additional mechanical bending strain on the inner cable at this point, because the rest of the cable is stiffer, potentially leading to cable failure where it enters the plug. There is also the potential for a loose un-bonded braid to come into contact with live terminals inside the plug.

In most cases, a standard heavy-duty un-braided flex should be sufficient (assuming it is a normal centre-tapped 110V application). Cables should be regularly checked for damage and replaced if necessary.

Individuals or employers supplying or condoning the use of inappropriate installations should be warned of these hazards.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
The British Approvals Service for Cables (BASEC)
23 Presley Way, Crownhill,
Milton Keynes MK8 0ES
Tel: 01908 267300
Fax: 01908 267255
Email: mail@basec.org.uk
Web: www.basec.org.uk
blue arrow pointing right   BASEC

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: BASEC & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can armoured cable be placed in PVC conduit?
Q & A of the Day – Should there be a separate CPC in parallel with cable armour?
Q & A of the Day - Can PVC cable protection be damaged by other insulation types?
Q & A of the Day – Can armoured cable be placed in conduit?
Q & A of the Day - For extension lead three-core flex, is there a colour requirement ?
Q & A of the Day - What is the best cable to use for sub-mains?
Q & A of the Day - Is 2.5mm2 stranded twin & earth cable OK in this house?
Q & A of the Day - Why is this conductor insulation lighting my neon screwdriver?