Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning the re-wiring a chip shop and the regulations regarding use of RCDs, is answered by SELECT:

Do domestic RCD regs apply to chip shops?
Do domestic RCD regs apply to chip shops?
pixel
Question: I'm currently re-wiring a chip shop. In this establishment there are fridges, freezers, fly killers and an emergency lighting system, as well as three-phase equipment. All of this electrical equipment is fed from an existing three-phase board that is only two years old.

Could you please advise me on whether the same regulations for RCDs in domestic property apply to commercial properties?

Answer: If you are re-wiring the chip shop, then similar regulations apply when the installation is used by ordinary persons - i.e. RCD protection for socket-outlets less than 20A and used by ordinary persons for general use, and for cables that may be buried less than 50mm deep and which are not suitably protected by earthed metallic protection.

If however, in such a commercial establishment as you describe, the installation is under the supervision of a skilled or instructed person, then RCD protection may not be required. You will need to establish whether this will be the case or not.

Generally speaking, the premises would normally be under the control of a supervisor or manager who should be aware of the dangers that electricity can create and who can adequately supervise and/or instruct the staff.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?