Q & A of the Day - What cable size in this installation?

BookmarkThis 18.08.2010
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning five new circuits of light loads and the right cable size to choose, is answered by SELECT:

Question: Fitting a new 24-way three-phase distribution board with a 200A main switch, cable is SWA run on cable tray for 10m with an ambient temperature of 25oC. The new board is only to supply approximately five new circuits of light loads initially. With no idea what it will supply in the future, what cable size would you suggest I use?

Answer: Guidance on determining the size of a cable to be used is given in Appendix 4 of BS 7671:2008.

You will first need to determine the design current from the estimated load. You will be unable to follow the design sequence until you have this information, together with the supply characteristics.

As voltage drop may be the overriding factor, this may then be obtained by consulting the relevant table - probably Table 4E4, in this case, for the sub-main cable. Remember, however, to add the voltage drop for the final circuits.

A protective device can then be chosen which has a rating not lower than the design current. The cable size can then be determined taking into account any correction factors and consulting Table 4E4. You will then need to check that Zs values will be satisfactory for the protective devices and the adequacy of earthing arrangements.

Further guidance can be found in the IEE Electrical Installation Design Guide.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?