Q & A of the Day - What is the likely electrical load for this marina?

BookmarkThis 10.08.2010
ECA
 

This Q and A of the Day from our Technical Expertise area, regarding the electrical load for a marina project, is answered by ECA experts (theme - power):

What are marina power demands?
What are marina power demands?
pixel
Question: I'm looking for an idea about the likely power demand/supply required for a new marina project.

The Marina: There are 200 berths for boats from 8 to 18m long. Typically, all the boats plug into the shore supply via an inverter when docked to trickle-charge their batteries. Then when aboard, and still on the marina, they will typically run a TV, radio and the lights (via the inverter). However, this would only apply to a maximum of 25% of the boats at any one time (say 50 boats).

In the winter, a fair number of boats (say 30%) run a dehumidifier 24 hours a day. When people stay aboard in the winter, then they might also run an electric fire, but - again - this would only be a small proportion at any one time (say 15%).

Pontoon: Lighting will be around 100 bollard lights, possibly LED.

Amenity block ashore: There will be an amenity block ashore for toilets and showers with lighting, electric heating, electric hand dryers (x6), electric showers (x6), two washing machines and two dryers (occasional use).

Any help on the likely power demand would be greatly appreciated.

Answer: As a simple guide only to give you an indication of the likely power requirement for the craft, it could be in the order of 1.5kVA for craft up to 12m long, 2.5kVA for craft 13m to 25m, and at least 4kVA for craft over 25m.

For the rest of the installation, guidance is provided in Appendix H of Guidance Note 1 Selection and Erection - produced by the IET.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
Electrical Contractors' Association (ECA)
ECA Head Office, ESCA House, 34 Palace Court,
London W2 4HY
Tel: 020 7313 4800
Fax: 020 7221 7344
Email: electricalcontractors@eca.co.uk
Web: www.eca.co.uk
blue arrow pointing right   ECA

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: ECA & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Is this 1970s electrical installation still OK today?
Q & A of the Day - Please clarify how to connect this smoke alarm circuit?
Q & A of the Day - Should a wind turbine supply cable be earthed both ends?
Q & A of the Day – What testing is needed for this altered domestic kitchen circuit?
Q & A of the Day – Is this garage sub-distribution board earth CPC adequate?
Q & A of the Day – Are smoke detectors necessary for this toilet?
Q & A of the Day – Can I use this T&E cable as the sub-distribution board CPC?
Q & A of the Day – What connection for this circuit having an extra consumer unit?
Q & A of the Day – Can I use T&E cable for this sub-distribution board CPC?