Can structural steel can be bonded to earthing protection?
Can structural steel can be bonded to earthing protection?
pixel
Question: Does structural steel require to be bonded to earth as per British Standards and BS 7430?

Answer: Clause 21.4 contained in BS 7430:1998 provides guidance on typical main equipotential bonding, and includes recommendations where earthed equipotential bonding and automatic disconnection of supply (EEBADOS - now referred to as Automatic Disconnection of Supply in BS 7671:2008) is used as the protective measure and recommends that extraneous conductive parts such as main water pipes, main gas pipes, and exposed metallic parts of the building structure are bonded to the main earthing terminal.

This is similar to requirements contained in BS 7671:2008 specifically in regulation 411.3.1.2, which requires main bonding conductors to connect to the main earthing terminal extraneous conductive parts - including water installation pipes, gas installation pipes and exposed metallic structural parts of the building.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?