Q & A of the Day – Must I separately link earth bars on this dis-board?

BookmarkThis 21.06.2010
Eaton
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning Memshield 2 or 3 Type ‘B’ three-phase boards and earth bars, is answered by Eaton:

Must I separately link earth bars on this dis-board?
Must I separately link earth bars on this dis-board?
pixel
Question: Is it necessary to separately link the two earth bars on the Memshield 2 or 3 TP distribution boards?

Answer: On the Memshield 2 or 3 Type 'B' three-phase boards, it is NOT necessary to link both earth bars (left- and right-hand) together, as they are already sufficiently connected via the case of the enclosure. Each individual bar is fastened to the case via an earthing strap, and hence to each other via the case.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
Eaton Electric Ltd.,
Reddings Lane, Tyesley,
Birmingham, B11 3EZ
Tel: 0121 685 2100
Email: tariqhussain@eaton.com
Web: www.eatonelectrical.com
blue arrow pointing right   Tariq Hussain - Eaton

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: Eaton & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Are LEDs dimmable?
Q & A of the Day - Can I reduce the cable lengths of an SPD?
Q & A of the Day - Why can't I use an RCD in a TN-C earthing system?
Q & A of the Day - What is the advantage of breaking the neutral on a switch?
Q & A of the Day – Do I need to fit a new switch to this distribution board?
Q & A of the Day – What is the maximum Zs value for a 400A HRC fuse?
Q & A of the Day - Switchgear - how to detect 'dead bus'?
Q & A of the Day - Why can't I use an RCD in a TN-C earthing system?