Q & A of the Day - What is the minimum conduit size needing sealing to prevent fire spread?

BookmarkThis 04.06.2010
BASEC (The British Approvals Service for Cables)
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning conduit and minimising the spread of fire, is answered by BASEC:

What minimum size of conduit?
What minimum size of conduit?
pixel
Question: With reference to Section 527 BS7671: 2008 (the 17th Edition), 'minimise the spread of fire', I understand that there is a minimum size of conduit that requires internal sealing to prevent the spread of fire.

What is this size? Also, where can I find that size stated in the Regulations?

Answer: See clause 527.2.6 on page 108.

Under clause 527.2.6, suitable conduit of maximum internal size 710mm2 does not need to be fire stopped if it complies with specific requirements. The size equates to a square of 26mm by 26mm, or a diameter of 30mm.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
Contact: Dr Jeremy Hodge
The British Approvals Service for Cables (BASEC)
23 Presley Way, Crownhill,
Milton Keynes MK8 0ES
Tel: 01908 267300
Fax: 01908 267255
Email: mail@basec.org.uk
Web: www.basec.org.uk
blue arrow pointing right   BASEC

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: BASEC & James Hunt

Related information

Related contacts

More News...

Q & A of the Day - Is there a colour requirement for extension lead three-core flex?
Q & A of the Day - Why is this phase conductor insulation lighting my neon screwdriver?
Q & A of the Day - SY cable braids cannot simply be cut off and taped, can they?
Q & A of the Day - Can I use a larger cable for a final circuit than the consumer unit feed?
Q & A of the Day - CPC sizes in twin & earth cable - is there a table?
Q & A of the Day – What is the minimum conduit size needing sealing to prevent fire spread?
Q & A of the Day – Is PVC cable protection damaged by other insulations?
Q & A of the Day – Can I use a larger cable for a final circuit than the consumer unit feed?