Q & A of the Day - In a brick party wall, must sockets be fire rated?

BookmarkThis 28.05.2010
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, about a flat conversion with a brick party wall, and fire rating of sockets, is answered by SELECT:

Stud walls - must sockets be fire rated?
Stud walls - must sockets be fire rated?
pixel
Question: On a flat conversion, we have built a stud wall in front of brick party wall and insulated the stud wall with rockwall slab and 12.5 mm plasterboard on top. Do the two x sockets have to be fire rated?

Answer: Guidance provided in the Scottish Building Standards Domestic Technical Handbook would define the brick party wall as a separating wall (it is designed to prevent fire spreading to the adjoining property)and requires that service openings and penetrations through such walls are protected from the effects of fire.

It is also a requirement that flush accessories are not installed in timber framed fire separating walls - the wall you have constructed is not likely to be the separating wall( the brick wall being the separating wall) therefore sockets can be installed.

It may, however, be advisable to install intumescent pads within each socket outlet box to prevent any adverse effects to the separating wall in the event of a fire. It may also be advisable to seek the advice of the local building control officer before proceeding with the work.

If you are under Part P of the Building Regulations in England or Wales, you will need to seek advice via the Part P advisory service.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?