Q & A of the Day - Will earthing genset earth to lightning protection satisfy the 17th Edition?

BookmarkThis 27.04.2010
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, about a standby generator, earthing and the lightning protection system, is answered by SELECT:

Genset earth to lightning protection?
Genset earth to lightning protection?
pixel
Question: Will connection of a standby generator earth to the lightning protection system earth, satisfy the requirements of regulation 551.4.3.2.1 in BS 7671: 2008?

Answer: With regards to a standby generator, Regulation 551.4.3.2 refers to the need for an additional means of earthing, such as an earth electrode. The resistance of this earth electrode should generally not exceed 20ohms. (see BS 7430 - CoP for Earthing - soon to be updated).

For lightning protection, prior to connection to the earthing system, the advice of a competent person, who is conversant with BS EN 62305:2006, should be obtained.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?