Q & A of the Day - What size of main equipotential bonding?

BookmarkThis 19.03.2010
ECA
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning equipotential bonding of a public building, is answered by the ECA:

What size main equipotential bonding?
What size main equipotential bonding?
pixel
Question: What is the recommended size for the main equipotential bonding of a public building with its own transformer supply and 500mm tails?

Note that the maximum I can find is for 300mm tails, which is 50mm. Do I need to increase to 70mm? Also, do I need to earth the lighting conductor?

Answer: Subject to the design details of your building, 50mm may be acceptable.

And yes, the lightning protection system should be connected to the building main earth bar/terminal?

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
The Electrical Contractors' Association (ECA)
ECA Head Office, ESCA House,
34 Palace Court, London W2 4HY
Tel: 020 7313 4800
Fax: 020 7221 7344
Email: electricalcontractors@eca.co.uk
Web: www.eca.co.uk
blue arrow pointing right   ECA

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: ECA & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I use T&E cable for this sub-distribution board CPC?
Q & A of the Day – At what point in this circuit should I do PSCC / PFC tests?
Q & A of the Day - Please show me where I can see a library of electrical symbols?
Q & A of the Day - Do I legally need to be associated to a governing body?
Q & A of the Day - Are there any BS or IEC standards for cable segregation?
Q & A of the Day – Does Part P cover holiday lodges?
Q & A of the Day – Do pipes in a workshop carrying oil need a main earth bond?
Q & A of the Day - Electrical fittings – can I replace them without notification?
Q & A of the Day - Does the control gear mess up lighting circuit test readings?