Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning TN-C earthing systems and RCDs, is answered by Eaton MEM:
|
| Why not use an RCD in a TN-C system? |
|
Question: Why can't I use an RCD in a TN-C earthing system?
Answer: In TN-C (and IT) networks, residual current devices (RCDs) are far less likely to detect an insulation fault. In a TN-C system they would also be very vulnerable to unwanted triggering from contact between earths of circuits on different RCDs or with real ground, so making their use impractical.