Q & A of the Day – What is the minimum cable CSA required for

BookmarkThis 04.01.2010
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, about cable tray and ladder and the minimum cable CSA required for earth bonding, is answered by SELECT:

Look it up in Table 54.8 (BS7671: 2008).
Look it up in Table 54.8 (BS7671: 2008).
pixel
Question: What is the minimum cross-sectional area of earthing cable required for the earth bonding of cable trays and ladders?

Also, what is the minimum cross-sectional area of earthing cable for the earth bonding of IT cable trays?

Answer: Unless the metal cable support system introduces a potential that does not already exist in the location in which the system is installed, it would not need to be bonded.

However, in practice you would normally bond the cable tray to prevent any potential coming into the building from any another location.

You should use Table 54.8 from BS7671: 2008 (the 17th Edition) to determine the correct size of conductor.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   admin@select.org.uk

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?