What CPC CSA's for twin & earth cable?
What CPC CSA's for twin & earth cable?
pixel
Question: Is there a table that lists CPC cross-sectional area (CSA) within modern twin and earth cables? If not, how is the CSA calculated for filling in the installation certificate?

Answer: The nominal sizes for CPCs for flat twin and earth cable are listed in each of the relevant BS standards. The regular cable type you describe is to BS 6004 Table 8.

For two and three conductor cables:

  • 1.5 sqmm cable has 1.0 sqmm CPC
  • 2.5 sqmm cable has 1.5 sqmm CPC
  • 4 sqmm cable has 1.5 sqmm CPC
  • 6 sqmm cable has 2.5 sqmm CPC
  • 10 sqmm cable has 4 sqmm CPC
  • 16 sqmm cable has 6 sqmm CPC

Please note that these are nominal sizes.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
Contact: Dr Jeremy Hodge
The British Approvals Service for Cables (BASEC)
23 Presley Way, Crownhill,
Milton Keynes MK8 0ES
Tel: 01908 267300
Fax: 01908 267255
Email: mail@basec.org.uk
Web: www.basec.org.uk
blue arrow pointing right   BASEC

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: BASEC & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Should there be a separate CPC in parallel with cable armour?
Q & A of the Day - Can PVC cable protection be damaged by other insulation types?
Q & A of the Day – Can armoured cable be placed in conduit?
Q & A of the Day - For extension lead three-core flex, is there a colour requirement ?
Q & A of the Day - What is the best cable to use for sub-mains?
Q & A of the Day - Is 2.5mm2 stranded twin & earth cable OK in this house?
Q & A of the Day - Why is this conductor insulation lighting my neon screwdriver?
Q & A of the Day - Extensions using SY braided cables - can the 16A plugs be right?
Q & A of the Day - Can CO detectors be wired from the lighting circuit supply?