Q & A of the Day – What is the minimum conduit size needing sealing to prevent fire spread?

BookmarkThis 24.11.2009
BASEC (The British Approvals Service for Cables)
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning conduit and minimising the spread of fire, is answered by BASEC:

Look at clause 527.2.6 to help prevent this!
Look at clause 527.2.6 to help prevent this!
pixel
Question: With reference to Section 527 BS7671: 2008 (the 17th Edition), 'minimise the spread of fire', I understand that there is a minimum size of conduit that requires internal sealing to prevent the spread of fire.

What is this size? Also, where can I find that size stated in the Regulations?

Answer: See clause 527.2.6 on page 108.

Under clause 527.2.6, suitable conduit of maximum internal size 710mm2 does not need to be fire stopped if it complies with specific requirements. The size equates to a square of 26mm by 26mm, or a diameter of 30mm.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
Contact: Dr Jeremy Hodge
The British Approvals Service for Cables (BASEC)
23 Presley Way, Crownhill,
Milton Keynes MK8 0ES
Tel: 01908 267300
Fax: 01908 267255
Email: mail@basec.org.uk
Web: www.basec.org.uk
blue arrow pointing right   BASEC

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: BASEC

Related information

Related contacts

More News...

Q & A of the Day – Can armoured cable be placed in PVC conduit?
Q & A of the Day – Should there be a separate CPC in parallel with cable armour?
Q & A of the Day - Can PVC cable protection be damaged by other insulation types?
Q & A of the Day – Can armoured cable be placed in conduit?
Q & A of the Day - For extension lead three-core flex, is there a colour requirement ?
Q & A of the Day - What is the best cable to use for sub-mains?
Q & A of the Day - Is 2.5mm2 stranded twin & earth cable OK in this house?
Q & A of the Day - Why is this conductor insulation lighting my neon screwdriver?
Q & A of the Day - Extensions using SY braided cables - can the 16A plugs be right?