Q & A of the Day - What should the main earth and bonding conductor size be?

BookmarkThis 09.10.2009
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning PME system main earth and bonding conductor sizing, is answered by SELECT:

What conductor size?
What conductor size?
pixel
Question: Can you please advise on the following:

We have been asked to carry out an electrical installation to a design provided by a consulting engineer. The main supply authority cable is 300mm2 and is a PME system. The cable tails from the supply authority cutout are 185mm2. The consultant has indicated that the main earth is to be 95mm2 and the main bonding conductors are to be 25mm2.

We feel that the main earth and bonding conductors should be 50mm2 (based upon Clauses 542.3.1 and Table 54.8 of the Wiring Regulations). Can you advise?

Answer: From the information provided, it would appear that the main earthing conductor should be 95mm2 (unless calculation allows a smaller conductor), and the main bonding would then be a minimum of 35mm2. Both selections should be the responsibility of the installation designer.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Is this 1970s electrical installation still OK today?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day - Please clarify how to connect this smoke alarm circuit?
Q & A of the Day - Should a wind turbine supply cable be earthed both ends?
Q & A of the Day – What are the difference types of automatic transfer switch (ATS)?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?