Insulation and its potentially hazardous effects on electrical installations - September's Speakers' Corner

Voltimum
 
Do you have a burning issue you'd like to discuss on Voltimum and to your industry peers? Get it off your chest and give us an email. This month's letter is from Arthur Day (electrical contractor) partner, Kevin Day.

Having had a recent NICEIC annual inspection visit, discussions with the inspecting engineer made it very clear that many installations will no longer meet BS 7671 standards with regard to conductor size/ current carrying capacity (ccc) and protective device coordination. Many existing installations will have been installed to BS 7671 16th edition. For instance, a 32 amp ring main would normally have been wired in 2.5mm twin + 1.5 mm earth cable. Especially in a bungalow having a solid floor, this cable would have typically been covered with a thin layer of insulation and would have met the regulations with regard to  coordination.

Many loft insulation firms have recently started upgrading loft insulation to 200mm with little or no regard to the effect said upgrading will have on electrical circuits. Because of the 0.51 factor which has to be applied to the ccc of the cable in this instance, it is clear that when using installation method 101, that the cable will only effectively carry around 12.5 amps. This results in a fairly well loaded ring main posing a potential fire risk (for this reason, a 4.0 mm twin + 2.5 mm earth cable would now usually be installed).  

If a periodic inspection is carried out on the property, a deviation code of 2 would have to be applied to the ring circuit described and drastic action recommended to be taken to amend the situation (ie rewiring with larger cables), moving the cables out of the insulation or lifting the insulation above the cables. I am surprised that there seems to be no one taking action to prevent insulation installers from burying cables in ths manor or that the issue is not raised more frequently by building control inspectors.

I would be interested in feedback from voltimum readers.  Are there similar experiences  and any remedies which could be cheaply applied retrospectively by anyone finding themselves in this situation.

Sincerely,

Kevin Day (Arthur Day Electrical).

Want to respond to Kevin's letter?  Send us an email here.


 Related contacts
3rd Floor
Bishops House,
25-29 Fulham High Street,
London
SW6 3JH
Telephone: 0207 751 3900
Fax: 0207 751 3901
blue arrow pointing right   Voltimum News Enquiry Email

Source: Voltimum
 Back

Related information

Related contacts

More News...

Level 3 qualification to become the minimum requirement for all new Qualified Supervisor applications – Letters to the Editor
British Standards/IEE Regulations and the Judicial System - Letter to the Editor
A loft wiring horror story - November's Speakers' Corner
Response to insulation and its potentially hazardous effects on electrical installations - October's Speakers' Corner
Part P: Too little too late - May's Speakers' Corner
If Part P is right and proper then the institution of the apprenticeship is dead - April's Speakers' Corner