Q & A of the Day - Can we install electrical equipment inside an explosive store?

BookmarkThis 02.09.2009
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning electrical equipment associated with an explosive store, is answered by SELECT:

Equipment must be suitable.
Equipment must be suitable.
pixel
Question: Can we install lighting switch and fire alarm devices inside an explosive store, or should we install this equipment outside?

Answer: Equipment in these areas needs to be suitable for installation in the hazardous zones. If it has not been specifically designed for use in hazardous areas, then the equipment should be installed outside the location.

Voltimum Managing Editor James Hunt says: 'Areas where flammable or explosive fluids, liquids, vapours and dusts are found, or are likely to be found, are called 'Hazardous Areas'. Hazardous areas are defined in The Dangerous Substances and Explosive Atmospheres Regulations 2002 (DSEAR) as 'any place in which an explosive atmosphere may occur in quantities such as to require special precautions to protect the safety of workers'. In this context, 'special precautions' is best taken as relating to the construction, installation and use of apparatus, as given in BS EN 60079 -10.

For more on hazardous areas in general, go to: www.voltimum.co.uk/cm.jsp?action=view&cat=135&universe=consult.experts_hottopics.FireSafAndSec.Atex

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?