Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning electrical supply to an outhouse in the back garden, is answered by SELECT:
|
| Use the distributor’s earthing facility? |
|
Question: In a TN-C-S system, where I have installed a three-core SWA supply to an outhouse approximately 20m down the back garden - in this system, does it mean that I cannot use the distributor's earthing facility?
I would appreciate if you could let me know what options I have.
Answer: Yes - you can use this TN-C-S system to provide an earth connection for the armour and equipment in the garden shed.
To see many more Q & A in Voltimum UK's Experts Area, please click on the link: www.voltimum.co.uk/consult.php?universe=consult.index.questions
|