Q & A of the Day - Can I use this RCBO for a domestic lighting circuit?

BookmarkThis 30.06.2009
ABB
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, about use of an RCBO to protect a domestic lighting circuit, is answered by ABB:

Can one use an RCBO for this application?
Can one use an RCBO for this application?
pixel
Question: Knowing the advantages of using Type C devices, can one use a 6A BS EN 61009-1 Type C RCBO for a domestic lighting circuit that has a 1mm CPC?

I have read, in the newly published On-Site Guide pg 104 Table 2D, that the minimum protective conductor size recommended for such Type C devices is 1.5/2.5mm, depending on fault level.

Answer: When using RCBOs you should use the guidance relating to RCDs rather than the MCB part when considering protective conductor sizing. This is because it is the RCD that will act on faults to earth at a much lower current (30mA typically) compared with the 60A from the C curve MCB characteristic.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
ABB Ltd.,
Tower Court, Foleshill Enterprise Park,
Courtaulds Way, Coventry CV6 5NX
Tel: 02476 368500
Fax: 02476 364499
Email: marketing.info@gb.abb.com
Web: www.abb.co.uk
blue arrow pointing right   ABB

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: ABB & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – How can I reverse the rotation of this star-delta motor?
Q & A of the Day - Do switchgear / service points have distance requirements?
Q & A of the Day - For PFC capacitors, how do I calculate kVAr?
Q & A of the Day - Should I test RCBOs at the distribution board?
Q & A of the Day - Why does this freezer fuse keep blowing?
Q & A of the Day - Is this motor re-wind faulty?
Q & A of the Day - Can we avoid having to buy seven RCBOs?
Q & A of the Day - How do I set a DOL starter motor overload relay?
Q & A of the Day - Is a switchfuse rating 'per phase'?