Q & A of the Day – Can SY cable steel wire braiding be used as a CPC?

BookmarkThis 09.06.2009
BASEC (The British Approvals Service for Cables)
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, about SY cable steel wire braiding, is answered by BASEC:

SY braided steel wire cable.
SY braided steel wire cable.
pixel
Question: Can the steel wire braiding of a two-core SY cable be used as a circuit protective conductor (CPC), or is the braiding only for physical protection and a three-core SY cable be used?

Answer: The braiding on a cable, such as SY, is not intended as a CPC (for UK Wiring Regulations purposes), so a suitable core should be used. Such braiding is intended as mechanical protection.

If the installation is within the scope of the IEE Wiring Regulations BS 7671 (17th Edition), and as this cable type is not specifically listed in the Wiring Regulations, a verification of safety needs to be conducted in accordance with Clause 511, and appropriate details of the departures from BS 7671 entered on the installation certificate.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
The British Approvals Service for Cables (BASEC)
23 Presley Way, Crownhill,
Milton Keynes MK8 0ES
Tel: 01908 267300
Fax: 01908 267255
Email: mail@basec.org.uk
Web: www.basec.org.uk
blue arrow pointing right   BASEC

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: BASEC & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can armoured cable be placed in PVC conduit?
Q & A of the Day – Should there be a separate CPC in parallel with cable armour?
Q & A of the Day - Can PVC cable protection be damaged by other insulation types?
Q & A of the Day – Can armoured cable be placed in conduit?
Q & A of the Day - For extension lead three-core flex, is there a colour requirement ?
Q & A of the Day - What is the best cable to use for sub-mains?
Q & A of the Day - Is 2.5mm2 stranded twin & earth cable OK in this house?
Q & A of the Day - Why is this conductor insulation lighting my neon screwdriver?
Q & A of the Day - Extensions using SY braided cables - can the 16A plugs be right?