Q & A of the Day – Does this flat’s main earth need upgrading?

BookmarkThis 07.04.2009
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning re-wiring a flat, including main bonding work, is answered by SELECT:

A typical installation with 16mm2 main earth.
A typical installation with 16mm2 main earth.
pixel
Question: I have just looked at a job that requires a new consumer unit and main bonding to gas and water. The submain feeding the flat is approximately 6m in length and consists of a 16mm twin & earth cable (with 6mm CPC) fed from the main communal meter cupboard by 60A fusewire / isolator (Wylex).

Does the main earth to the flat concerned need upgrading from 6mm to 16mm and, if so, can I run it in surface minitrunking around the communal area up to the flat?

Answer: The earthing conductor should be upgraded to 16mm2.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?