Q & A of the Day – How do we calculate the PSC at the design stage?

BookmarkThis 17.02.2009
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, about prospective short circuit (PSC) values of protective devices, is answered by SELECT:

The IEE's 'Electrical Installation Design Guide'.
The IEE's 'Electrical Installation Design Guide'.
pixel
Question: With a three-phase TT supply, how do we define and calculate the prospective short circuit (PSC) values of protective devices at the design stage. Also, how do we calculate the size of the main earth?

Answer: The calculation of the PSC for three-phase fault is quite complicated, but - as a rule of thumb - it is generally 2 x single phase PSC. You could either enquire via the distributor, calculate or measure.

For the size of the main earth, you can either select via Table 54.7 in BS7671: 2008, or use the adiabatic equation.

For reference, you may want to refer to the latest Electrician's Guide issued by the IEE (www.theiet.org) entitled: 'Electrical Installation Design Guide'. This is readily available and costs about £20.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?