Q & A of the Day – Should upstairs lights be on a separate RCD?

BookmarkThis 21.01.2009
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, about BS7671: 2008 and whether upstairs lights should be on a separate RCD, is answered by SELECT:

A separate RCD for lighting upstairs?
A separate RCD for lighting upstairs?
pixel
Question: Is there a recommendation about which circuits should be fed from alternate RCDs (i.e., should upstairs lights be on a separate RCD, compared with downstairs lights etc?

Answer: There is no specific requirement for how circuits should be divided - see Section 314 of the Regulations (BS7671: 2008), which deals with division of the installation.

Generally, most contractors will put downstairs lights/upstairs sockets on one RCD, and upstairs lights/downstairs sockets on the second RCD, and so on. This will help, as best as possible, against the effects of nuisance tripping.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?