Q & A of the Day – A TT system with earth spike or a TNC-s?

BookmarkThis 22.12.2008
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning a property re-wire and whether to use a TT system with an earth spike or a TNC-s system, is answered by SELECT:

Use an earth spike?
Use an earth spike?
pixel
Question: I am currently undertaking a re-wire to a property built circa 1960s. I believe that the supply to be a TN-s system as the original earth was taken from the metal casing where the incoming cable was terminated and was 4mm CSA! There is no clamp on the armour of the incoming cable.

When I performed a Ze on the original earth, I recorded readings of 800 ohms plus. Will I have to change the system to a TT and install an earth spike, or is it acceptable to change the system to a TNC-s by connecting into the neutral block. Alternatively, is it the responsibility of the distributor to supply the earth connection?

Answer: The distributor is not obliged to provide an earth for an existing installation. If no earth is present, the distributor should be consulted regarding the provision of an earthing facility but, if willing to do so, it may charge for such provision.

If the distributor is not willing to provide an earth, or the client will not pay for its provision, the only option is to provide a TT earthing system. Use of the supply neutral connection as the means of earthing is not an option.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?