Question: I recently conducted a phase loop test on an existing installation and the value I got was 6.7ohms. Is this value low enough to allow a fault current to flow in order to operate the protective device? If not, what is the acceptable value?
Answer: Depending on the type of protective device, the maximum earth fault loop impedance values should comply with table 41B2 or 41B1 from BS7671 : 2001.