A genset - but how to detect 'dead bus'?
A genset - but how to detect 'dead bus'?
pixel
Question: I have two generators feeding unto a busbar via an automatic changeover switch. I want to feed the same busbar with a standby generator. What do I do to detect dead bus before switching the standby source to the board?

Answer: Please confirm the serial number of the assumed existing Eaton equipment in order that we can establish the product type.

Is there any synchronising control? Mechanical interlocking may be required to ensure that the third supply is not in parallel with the existing supplies. Voltage sensing will normally be located on the live side of the incomers.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
Eaton MEM Circuit Protection & Control
Reddings Lane, Tyseley,
Birmingham B11 3EZ
Tel: 08700 545 333
Fax: 0121 706 2012
Email: ukcommorders@eaton.com
Web: www.eatonelectrical.com
blue arrow pointing right   Eaton MEM

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: Eaton MEM & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – What are the difference types of automatic transfer switch (ATS)?
Q & A of the Day - Is breaking the neutral on a switch beneficial?
Q & A of the Day – Why not use an RCD in a TN-C earthing system?
Q & A of the Day – Is there an advantage in breaking the neutral on a switch?
Q & A of the Day - Can I reduce the cable lengths of an SPD?
Q & A of the Day – Must I separately link earth bars on this dis-board?
Q & A of the Day – Are LEDs dimmable?
Q & A of the Day - Can I reduce the cable lengths of an SPD?
Q & A of the Day - Why can't I use an RCD in a TN-C earthing system?