Q & A of the Day – In a school workshop, should fixed equipment be RCD protected?

BookmarkThis 09.10.2008
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning a school workshop and whether its fixed equipment should be RCD protected, is answered by SELECT:

School workshop - what protection is needed?
School workshop - what protection is needed?
pixel
Question: In a school workshop application, all standard sockets are protected by RCBOs. The fixed equipment, both single- and three-phase (i.e. lathes, drills, saws etc) is protected by MCBs, as recommended by manufacturers. The workshop has its own dedicated distribution board incorporating emergency stop circuitry solely for machinery / socket outlets. Is there a requirement to provide further protection via RCDs / RCBOs / RCCBs for the fixed items of machinery, taking into account the problems associated with nuisance tripping?

I attach the machinery schedule - click on the 'Downloadable Attachments' link below to download it (.PFD doc - 33.3kB).

Answer: There is no specific requirement in BS 7671 to provide RCD protection for the machinery circuits.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Downloadable attachment(s)
bluearrow  The machinery schedule (.PFD doc - 33.3kB).

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Downloadable attachment(s)
Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?