Q & A of the Day – Can I ignore this lighting circuit voltage drop?

NICEIC
 
Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning the maximum voltage drop on a lighting circuit, is answered by the NICEIC:

What maximum voltage drop for a luminaire?
What maximum voltage drop for a luminaire?
pixel
Question: BS7671:2008 gives a maximum voltage drop on a lighting circuit for a public supplied system as 3% (Table 12A - i). Am I allowed to ignore this value and work to the minimum luminaire voltage tolerances?

For example, taking a luminaire, the HF ballast of which can work down to a minimum voltage of 200V, and working to the lowest allowed supply voltage of 216.2V ( Uo - 6%), it would be allowed to have a voltage drop of an absolute maximum of 16.1V (Uo - 7%). Is that so?

I would never design using maximum limits but, if I was to design to ensure being within the luminaire's safe working limits, I would use a larger voltage drop than the 3% stated in BS7671. As far as I can see from looking through BS7671, I cannot find any note saying whether I can work to the voltage tolerances of equipment supplied instead of Table 12A.

Answer: Reference to Regulation 525.1 (p106) of BS7671:2008 requires the voltage at the terminals of equipment to be greater than the lower limit specified in the product standard for the equipment concerned. So, if these conditions were ensured, this would comply with BS7671:2008. The percentage approach given in Regulation 525.3 is usually applied where specific information concerning the load is unavailable at the time of design and hence is more onerous.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Related contacts
NICEIC Group Ltd.,
Warwick House, Houghton Hall Park,
Houghton Regis, Dunstable LU5 5ZX
Tel: +44 (0)1582 531 000
Fax: +44 (0)1582 531 010
Email: enquiries@niceic.com
Web: www.niceic.com
blue arrow pointing right   NICEIC

Source: NICEIC & James Hunt
 Back

Related information

Related contacts

More News...

Q & A of the Day – Is RCD protection needed for existing 16th Edition circuits?
Q & A of the Day - Do I need to replace the consumer unit?
Q & A of the Day - Can I work to minimum luminaire voltage tolerances?
Q & A of the Day - What procedure to follow when replacing a bathroom fan?
Q & A of the Day - Is this consumer unit in the right position?
Q & A of the Day – Nightclub work – Does it fall under Part P?
Q & A of the Day – What is the definition of Residential Accommodation?
Q & A of the Day – Problems with supply separation/interconnection within smoke alarm cables?