Q & A of the Day - Do I need to replace the consumer unit?

NICEIC
 
Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning an extra socket and whether this would mean replacing the entire consumer unit, is answered by the NICEIC:

Do I need to replace the consumer unit?
Do I need to replace the consumer unit?
pixel
Question: If an additional socket outlet or light was to be added to an existing circuit, say in an upstairs bedroom, would the whole consumer unit need replacing to comply with the 17th Edition?

Answer: The proposed alteration/addition only would be required to comply with BS7671 : 2008. However it should be noted that Regulation 131.8 requires verification of the existing arrangements to check that they are satisfactory and suitable for the proposed alteration/addition, including the earthing/bonding arrangements. Also Regulation 633.2 requires, as far as is reasonably practicable, any defects observed in the existing installation to be recorded on the certificate.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Related contacts
NICEIC Group Ltd.,
Warwick House, Houghton Hall Park,
Houghton Regis, Dunstable LU5 5ZX
Tel: +44 (0)1582 531 000
Fax: +44 (0)1582 531 010
Email: enquiries@niceic.com
Web: www.niceic.com
blue arrow pointing right   NICEIC

Source: NICEIC & James Hunt
 Back

Related information

Related contacts

More News...

Q & A of the Day – Can I ignore this lighting circuit voltage drop?
Q & A of the Day – Is RCD protection needed for existing 16th Edition circuits?
Q & A of the Day - Can I work to minimum luminaire voltage tolerances?
Q & A of the Day - What procedure to follow when replacing a bathroom fan?
Q & A of the Day - Is this consumer unit in the right position?
Q & A of the Day – Nightclub work – Does it fall under Part P?
Q & A of the Day – What is the definition of Residential Accommodation?
Q & A of the Day – Problems with supply separation/interconnection within smoke alarm cables?