Q & A of the Day – Why is this distribution board running at 40Hz?

Select
 
Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning a distribution board and unusual frequency readings, is answered by SELECT:

Distribution board - should be 50Hz.
Distribution board - should be 50Hz.
pixel
Question: I was testing a three-phase distribution board that supplies outdoor air conditioning units. The distribution board is supplied from the main incoming supply. I am getting a reading of 40Hz at the distribution board and also from any outdoor air conditioning units supplied from it, so my meter will not do an earth loop impedance test. I am also getting a reading of 50Hz at the main incoming supply and 0.08 loop impedance.

Can anyone please explain this? Also, would equipment running at 40hz not be damaged if it should be 50Hz? Would this have an effect on the earth loop impedance readings - not being below the maximum and not meeting disconnection times permitted?

Answer: You have not said what type of environment the installation is in - which may have given some insight.

There will probably be some electromagnetic interference in the installation, which can result in harmonic generation and interference.

Are the three-phase cable tails in the same entry hole in the distribution board? If not, then if the distribution board is of ferrous material, there may be magnetic interference. Also check the compatibility of any other electronic or control gear, which may also give rise to interference.

Harmonic voltages and currents can affect the operation of equipment and, in some circumstances, cause cables to be overloaded. Harmonics is a specialised subject and you may have to seek further advice if the above does not help.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

Source: SELECT & James Hunt
 Back

Related information

Related contacts

More News...

Q & A of the Day – Is a clean earth necessary for an IT server room?
Q & A of the Day – Can I supply the cooker hood from the main cooker supply?
Q & A of the Day – Calculating volt drop, which BS7671 table column should I use?
Q & A of the Day - Does a combi-boiler require supplementary bonding?
Q & A of the Day – Does agricultural machinery need isolation?
Q & A of the Day – Why is continuity of R1+R2 bigger than measured earth loop impedance?
Q & A of the Day – What testing on radial sockets from power busbars?
Q & A of the Day – What are protection requirements for socket in hazardous area?