Q & A of the Day - Is this consumer unit in the right position?

NICEIC
 
Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning whether, when replacing an old consumer unit, the new one should go in the same position, is answered by the NICEIC:

Move the consumer unit?
Move the consumer unit?
pixel
Question: I have to replace a consumer unit currently supplying lighting and immersion circuits (a second main unit is close to the meter and not part of this question). The current consumer unit is a four-way wired fuse type and is above a shelf approximately 8ft6in from the floor, accessible from stepladder.
However, the room it is situated in is a cloakroom with toilet and wash handbasin. Is it acceptable to replace this in that location, or should I move it close to the main unit? The circuits it supplies are perfectly acceptable and do not need replacing.

Answer: Consideration should be given to establish whether the consumer unit is suitable for the environment and accessible for inspection, testing and maintenance to be safely carried out. From the description, it would seem that splashing from the basin would be unlikely.

As regards accessibility, it is not unusual, but not ideal, for consumer unit to be located at this height. You should make your own assessment of how easy it would be to access it for maintenance purposes and then decide whether it requires relocating or not.

The relevant Regulations in BS7671 : 2008 are as follows: 132.12 p18, 513.1 p90.

The location for a consumer unit must provide reasonable access to facilitate the operation of switches and protective devices, and also facilitate inspection, maintenance and access to all connections. In the circumstances that you describe, at 8ft 6in (2590mm) from the floor in a cloakroom, it is difficult to see reasonable access being achieved and your suggestion of mounting the unit close to the main unit appears a better solution. See Regulations 132.12, 341.1 & 529.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Related contacts
NICEIC Group Ltd.,
Warwick House, Houghton Hall Park,
Houghton Regis, Dunstable LU5 5ZX
Tel: +44 (0)1582 531 000
Fax: +44 (0)1582 531 010
Email: enquiries@niceic.com
Web: www.niceic.com
blue arrow pointing right   NICEIC

Source: NICEIC & James Hunt
 Back

Related information

Related contacts

More News...

Q & A of the Day – Can I ignore this lighting circuit voltage drop?
Q & A of the Day – Is RCD protection needed for existing 16th Edition circuits?
Q & A of the Day - Do I need to replace the consumer unit?
Q & A of the Day - Can I work to minimum luminaire voltage tolerances?
Q & A of the Day - What procedure to follow when replacing a bathroom fan?
Q & A of the Day – Nightclub work – Does it fall under Part P?
Q & A of the Day – What is the definition of Residential Accommodation?
Q & A of the Day – Problems with supply separation/interconnection within smoke alarm cables?