Q & A of the Day – What testing on radial sockets from power busbars?

BookmarkThis 01.09.2008
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning radial sockets supplied from power busbars, and what testing is needed, is answered by SELECT:

A radial circuit fed by a consumer unit.
A radial circuit fed by a consumer unit.
pixel
Question: Can you please advise on what testing is required on radial sockets supplied from power busbars?

Answer: Radial sockets should not be supplied direct from power busbars - they should be supplied from an appropriate protective device. Then appropriate testing can be carried out, such as continuity (either R2 or (R1 + R2), insulation resistance and earth loop impedance etc.

It may be permissible to supply, say, a spur point (for example for the likes of main F/A switch) from the busbars, generally providing that the tails are no more than 3m in length. Testing of the tails would then entail isolation of the busbars prior to carrying out the appropriate testing.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?