Q & A of the Day – What are protection requirements for socket in hazardous area?

Select
 
Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning the protection requirements for the circuit feeding a socket in a hazardous area, is answered by SELECT:

Hazardous area - circuit protection requirements?
Hazardous area - circuit protection requirements?
pixel
Question: When installing a 110V socket in a hazardous area from a distribution board having a common transformer that is centre tapped to earth, what are the protection requirements for the circuit feeding the socket? And also, what are the protection requirements for feeding the transformer? Please note that the transformer is 3kVA rated.

Answer: You have not mentioned what hazardous area you are talking about. If this is a hazardous area such as a construction site etc., then as the transformer is centre tapped, both live poles should be protected against fault current. This can be provided by using suitable double pole circuit breakers, or may - in some instances - be provided by using a suitable thermostat embedded in the primary winding of the transformer. This will cut off the supply to the primary winding and hence isolate the secondary side.

There are hazardous areas where there are risks of explosion because of the presence of flammable substances. In such cases, the above arrangement would be unsuitable.

Picture of a hazardous area courtesy of Emerson Process Management. 

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

Source: SELECT & James Hunt
 Back

Related information

Related contacts

More News...

Q & A of the Day – Is a clean earth necessary for an IT server room?
Q & A of the Day – Can I supply the cooker hood from the main cooker supply?
Q & A of the Day – Calculating volt drop, which BS7671 table column should I use?
Q & A of the Day - Does a combi-boiler require supplementary bonding?
Q & A of the Day – Does agricultural machinery need isolation?
Q & A of the Day – Why is continuity of R1+R2 bigger than measured earth loop impedance?
Q & A of the Day – Why is this distribution board running at 40Hz?
Q & A of the Day – What testing on radial sockets from power busbars?