Q & A of the Day – Can I now use 230V power tools on construction sites?

ECA
 
Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day, concerning BS7671 and whether the Regulations now allow the use of 230V power tools on construction sites, is answered by the ECA:

An ITW power tool.
An ITW power tool.
pixel
Question: Regulation 704.410.3.10 / II says that automatic disconnection (Section 411) of supply with additional protection by an RCD having characteristics specified in Regulation 415.1.1 is suitable protection for a socket outlet up to 32A.

I am reading this as telling me that on construction sites we are now allowed to use 230V tools, if we meet these criteria. Is this the case?

Is the HSE happy with this? Or does HSE still require 110V? Any advice regarding this would be appreciated.

Answer: You can use a 230V tool on a construction site provided that it is protected by a 30mA RCD. The HSE has produced a publication concerning electricity on construction sites where this is also mentioned. However, 110V is still he most common and preferred option.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions


 Related contacts
Electrical Contractors' Association (ECA)
ECA Head Office, ESCA House,
34 Palace Court, London W2 4HY
Tel: 020 7313 4800
Fax: 020 7221 7344
Email: electricalcontractors@eca.co.uk
Web: www.eca.co.uk
blue arrow pointing right   ECA

Source: ECA & James Hunt
 Back

Related information

Related contacts

More News...

Q & A of the Day - What cable do I have to use as 100A sub-mains?
Q & A of the Day - Is grease is coming out of cables a problem?
Q & A of the Day – What is the size of earthing conductor I must use?
Q & A of the Day – What’s the minimum earth loop impedance for a domestic installation?
Q & A of the Day – What’s the best method of wiring up replacement equipment?
Q & A of the Day - Why should earth bonds be upgraded when installing consumer units?
Q & A of the Day – How to comply with 17th Edition lighting voltage drops?
Q & A of the Day - Is house rewiring in plastic trunking outside acceptable?