Q & A of the Day - Can I use orange for machine isolator supply cables?

BookmarkThis 11.08.2008
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, about the colour that machine isolator supply cables should be, is answered by SELECT:

Not orange in BS 7671!
Not orange in BS 7671!
pixel
Question: I have received a request from our EHS Department to colour-code orange the supply side cables of a machine isolator in order to identify them as being permanently live. I have questioned this because, as far as I am aware, this is not required under any electrical regulation. I have also pointed out that, if any maintenance work requires to be carried out, the equipment should be isolated by an electrically competent person who would be fully aware that the supply side would be live and advise other personnel of this fact. Is this correct? Please advise…

Answer: Conductors should be identified in accordance with Table 51 in BS 7671, three-phase line conductors to harmonised cable core colours being brown, black and grey. The colour orange would NOT meet this requirement.

Before gaining access to live parts of a machine, the isolating switch would require to be switched off. The incoming terminals at the isolator should be shrouded; the shroud bearing a warning that it covers live terminals.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – What is the allowable distance between sink and distribution unit?
Q & A of the Day – What is the phase-in period for the new EICRs?
Q & A of the Day – Was this transformer shock caused by static?
Q & A of the Day – What is meant by this fire rating term in the new EICR?
Q & A of the Day – Should PME earthing be used in a marina installation?
Q & A of the Day – How best to earth this old house’s electrical system?
Q & A of the Day - Can burned out electrical loads be cause by loose neutral conductors?
Q & A of the Day – What is the maximum flex length I can run to this rack?
Q & A of the Day – Can PVC cables in polystyrene insulation run in PVC conduit?