Q & A of the Day - Does this machine outdoors need MCB AND RCD protection?

BookmarkThis 01.08.2008
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning a machine fitted outdoors and the nature of the protection required, is answered by SELECT:

Fixed motor - no RCD required.
Fixed motor - no RCD required.
pixel
Question: I have to install a three-phase, 415V machine outdoors. Can I just protect the circuit using MCBs, or do I need to put in RCD protection? The machine will be permanently wired in a fixed position.

Answer: Generally, if the equipment is fixed, then there will be no requirement to have additional protection by means of an RCD. If the equipment used outdoors is mobile and its current rating does not exceed 32A, then additional RCD protection should be used.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?