Question: The NICEIC is saying that I do not need to have my insulation tester calibrated annually, provided that I carry out regular comparison testing on a resistive load. How then do I ensure that the meter continues to output the full 500V DC at 1mA into a 0.5 MegOhm load as specifically required by BS7671?

Output voltage and current may both fall, yet still provide correct resistance values acting as a simple multimeter.

Answer: We would recommend that you contact the NICEIC again to clarify its calibration recommendations. Our understanding is that the NICEIC recommends instrument verification checks in-between calibration. As you have correctly identified, you would need to purchase specific instruments to verify all aspects of your test instruments compliance to BS7671. There are check-boxes on the market that will indicate whether the correct voltage is attained at the relevant resistances but, as far as we are aware, these do not replace an annual calibration.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
Fluke (U.K.) Ltd.,
52 Hurricane Way, Norwich,
Norfolk NR6 6JB
Tel: +44(0)20 7942 0700
Fax: +44(0)20 7942 0701
Email: ukelectricalinfo@fluke.com
Web: www.fluke.co.uk/electrical
blue arrow pointing right   Fluke

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: Fluke & James Hunt

Related information

Related contacts

More News...

Q & A of the Day - Is there any test equipment that traces three-phase dis-board equipment?
Q & A of the Day - What is a ramp test?
Q & A of the Day - What is a ramp test?
Q & A of the Day - Electrical testing - how do I locate a circuit breaker?
Q & A of the Day - How to carry out touch voltage measurement?
Q & A of the Day - Does my insulation tester need annual calibration?
Q & A of the Day - Does my insulation tester need annual calibration?
Q & A of the Day – Is there test equipment available that traces three-phase distribution board equipment?